39EN
ISOM DIGIWARE - 546780C - SOCOMEC
IMPORTANT:
Screw on the "network to be monitored" connector of the ISOM Digiware L-60 to ensure the
insulation is monitored.
On all your ISOM Digiware devices, use RJ plugs at the RJ-45 connectors left free to prevent the
accumulation of conductive dust.
A single ISOM Digiware L-60 insulation monitoring device should be connected or active on each
network or interconnected IT circuit.
Always observe the auxiliary power supply voltage shown on the device: 24 VDC ± 10%.
Use a P30 24 VDC power supply, available as 30 W (ref. 4729 0603), or protect the device with a 1
A gG 24 VDC fuse.
Provide a 2A gG fuse on main voltage inputs.