43
Alarms 33 to 40
No. Description
Bit
mask Default
33 Loss of power 1 1
34 Fan alarm 4 2 2
35 Damper Feedback 4 0
36 Pre Filter 8 0
37 Pre HP C1 16 0
38 Pre HP C2 32 0
39 Reserved 64 0
40 Reserved 128 0
Factory Default Bitmask Total 3
Alarms 41 to 48- (Sensor Failure Alarms)
No. Description
Bit
mask Default
41 Return temperature 1 1
42 Return humidity 2 2
43 Remote temperature 4 4
44 Remote humidity 8 8
45 EWT1 temperature 16 16
46 LWT1 temperature 32 32
47 EWT2 temperature 64 64
48 LWT2 temperature 128 128
Factory Default Bitmask Total 255
Alarms 49 to 56- (Sensor Failure Alarms)
No. Description
Bit
mask Default
49 Circuit 1 discharge pressure 1 1
50 Circuit 1 discharge pressure 2 2
51 Economizer return temperature 4 4
52 Economizer return humidity 8 8
53 Economizer outdoor temperature 16 16
54 Economizer outdoor humidity 32 32
55 Reserved 64 64
56 Reserved 128 128
Factory Default Bitmask Total 255
Alarms 57 to 64- (Sensor Failure Alarms)
No. Description
Bit
mask Default
57 Static air pressure 1 1
58 Differential air pressure 2 2
59 Dewpoint 4 4
60 Airspeed 8 8
61 Circuit 1 suction pressure 16 16
62 Circuit 1 suction pressure 32 32
63 Circuit 1 suction temperature 64 64
64 Circuit 2 suction temperature 128 128
Factory Default Bitmask Total 255