81307063I
EN
20
Events
Event list stores individual events such as Pump starts/stops,Alarms,alarmtypesandwhenthealarmsoccur
andwhenitwasacknowledged.Thecontrollerstores4096time-stampevents.
Theeventlistisalwaysactiveforalarms.Toactivateeventlistforpumpstarts/stops,
Go into Settings – Common P1-P4 – Log pump events - Yes
2.8 If using CA 622; set up communications to surrounding units VFD, soft
starters and energy meters
SeeinstallationguideforCA622howtoconnectthesurroundingunits.Note:Allthesurroundingunitsmust
haveuniqueModbusID’sandsamecommunicationparameters.
2.9 Set up cleaner, mixer or drain (if used)
Ifusingcleaner,mixerordrainpump,adigitaloutputmustbesetascorresponding.
Cleaning
Thesettingsforcleaneraretobefound:
Settings – Cleaner
The cleaning can be done at pump start or at pump stop.
Flushing time in second
NumberofStarts to ushsettheintervaltohowmanystarts/stopsbeforecleaningstarts.
Mixer
Thesettingsformixeristobefound:
Settings – Mixer control
Themixercanbestartedafteracertainnumberofregularpumpstartsorafteratimeinterval.Thereisalsoa
criteriatosettheleveltobewithinacertainspan.Themixerruntimemustalsotobeset.
Thesettingsare:
Stop pump when mix [Yes/No]
Run indication [Yes/No]
Mixer run time
Pump starts to mix
Time interval to mix
Max level for start
Min level to start
Motor protector
Mixer alarms
Drain pump
Drainpumprequiresastartoatconnectedtoadigitalinputwhichissetasdrain pump oat. The settings for
drainpumpistobefound:
Settings – Drain pump
Thedrainpumprunsonlyontimesettings,thereisnostopoatforthedrainpump.