81307063I
EN
14
2.4 Congurethepumppitparameters
Table 2-5:
Pit settings
Level sensor type
Max number of pump running
Min time between relay change
Alternation
Alternative stop level
Start/stop on fast change
Station ow*
Calculation of pump capacity*
Overow
Backup running
Pit alarms
Pump blocking
Level sensor check
Tariff control
Level above sea
* MUST for accurate pump capacity calculation
Level sensor type (required parameter, default level sensor)
Analogsensororstart/stopoats.Analogsensorisrecommendedifyouwanttotrackthecapacityofthe
pumps and pumping volume.
Max number of pumps running (optional parameter)
Ifyourpipesystemcannothandletoohighows/pressureoryourpowergridhaslimitations,reducenumberof
pumps running at the same time. See section 3.4.1
Alternation (optional parameter)
Normalorasymmetrical
Normal:Thepumpsstartinsequencefrom1-4.Thereisalwaysonepumpstartattherst(lowest)startlevel.
Asymmetrical:Thepumpsaredividedintwogroupsthereonegroupisworkingmorefrequentlythantheother
group. See also section 3.4
Alternative stop level (optional parameter)
Thisfunctionistoaidreductionofsedimentsinthepitandavoidingoatingcrust
Start/stop on fast change (optional parameter)
Forexample:Ifthepumpstationispumpingclearwaterandaheavyrainllsthepitveryfast,thepumpcan
start before the level reach the start level.
Station ow (recommended parameters)
Under Meas. parameters set the Inow calculation=ONandyourpitshape,alsothefunctionEmptying or
Filling the pit must be set. System curve at duty pointisusedifthereisn’tanyOutlet pressure sensor.
Recommended is to setup the Pit area under Station ow.That’sbecausethepumpcalculationsshallpreform
as accurate as possible. This are bound to Energy calculation,Pump capacity and Outlet calculations. Best
accuracyofpumpcapacitycalculationsandpumpedvolumeiswhenanOutlet pressure sensor is used.
See section 3.2 for more information.
Calculation of pump capacity (recommended parameter)
Recommended to set Calculation=ON.Thelevelmustbeinthespanofminimumandmaximumduringthe
calculations.Makesurethatthealltimestogetherinstart delay/calculation time/stop delay in total must be in
one and the same pump sequence. See section 3.2 and forward.