EasyManua.ls Logo

Sulzer ABS PC 441 - Settings for Analog Inputs; Settings for Analog Outputs

Default Icon
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81307063I
EN
69
5.14 Settings for analog inputs
Table5-12showsthecompletelistofsettingsyoucanmakeunderthesubmenu Analog Inputs.
Table 5-12 Settings for analog
inputs,under‘Settings>AnalogInputs’
Submenu Submenu Setting Value Passcode Comment
Analog Input 1
Signal Range (4-20mA,0-20mA)
System
Dedicatedforthelevelsensor.
Filter Constant Seconds
Scaling0%= m,ft
Scaling100%= m,ft
ZeroO󰀨set m,ft
Analog Input 2
to
Analog Input 5
Filter Constant Seconds
If CA 442 is connected to a pump
the vibration input signal from CA
442 will be used instead of the
analog inputs in this menu.
If CA 443 is connected to a pump
the motor current from CA 443
will be used instead of the analog
inputs in this menu.
(NA=notavailable)
Input Function
(O FF,
NA,
Motorcurrentpump1,
Motorcurrentpump2,
Motorcurrentpump3,
Motorcurrentpump4,
Back-pressure,
Vibrations,
Freechoice,
Vibrationspump1,
Vibrationspump2,
Vibrationspump3,
Vibrationspump4,
XylemMiniCasSim.P1,
XylemMiniCasSim.P2,
XylemMiniCasSim.P3,
XylemMiniCasSim.P4)
Outowmeter
5.15 Settings for analog outputs
Table5-13showsthecompletelistofsettingsyoucanmakeunderthesubmenuAnalog Outputs.
Table 5-13 Settings for analog
outputs,under‘Settings>AnalogOutputs’
Submenu Submenu Setting Value Sub settings Passcode
PC 441
Main Module
Analog Output 1
Signal Range (4-20mA,0-20mA)
Scaling0%
Scaling100%
System
Filter Constant Seconds
Output Function
(O FF,
Pitlevel,
Pitinow,
Pitoutow,
Pitoverow,
Pulsechannel1,
Pulsechannel2,
Pulsechannel3,
Pulsechannel4,
PIDcontroller
DataRegister)
DataRegister0-4529
Scaling0%
Scaling100%
See Section 4.3

Table of Contents