EasyManua.ls Logo

Sulzer ABS PC 441 - Analog Output Type: Data Register; Mixer Prestart; Mixer and Drain Pump Blocking

Default Icon
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81307063I
EN
45
4.3 Analog output type: data register
WiththeAnalogOutputTypeData register,anyanalogsignal,actualorcalculatedcanbeusedasa0/4-20mA
outputsignal.ByusingtheregistersdenedintheModbusmanual,youcanachievethisfunction.
Example Wewanttohavea4-20mAanalogoutputsignaltiedtostatortemperature1onpump1.Wealsowanttheoutput
signal to be 4mA at 0°C and 20mA at 150°C.
NOTE! According to Comli/Modbus reference manual(p/n81307126)wendthatthetemperaturestatorpump1isin
register 40;seegure4-3below.Wenoteaswellthatthescalefactoris0.1(i.e. the value in reg.40 is multi-
plied by 0.1 to get actual value in engineering units).
Figure 4-3 AbovetableisanextractfromtheComli/ModbusmanualforPC441–
Analog inputs/Output in engineering units
The function is to setup in the menu of the CA 511 under; Settings / Analog outputs / PC 441 Main
(or CA 781 Exp.-) Module / Analog output 2 to [Data register] according to picture below.
Analogue Output 2 Output Range
Signal Range Data Register
[4-20 mA] 40
Filter Constant Scaling 0% =
1 s 0
Output Function Scaling 100% =
[Data Register] 1500
Esc
Scaling100%shouldcorrespondtothedatavalueat20mA,inthiscase1500for150°C.
AboveisanexampleofhowtocongureaPt100Statortemperaturetransmittedoutputasa4-20mAsignal
via Analog output.
4.4 Mixer prestart
IfMixerfunctionisselectedandthePC441isactingasa[Pump controller],theMixerwillbestartedbefore
therstpumpisstarted.Thisallowsthemixertimetospeedupbeforeanypumpisstarted.
ThisistrueiftheMixerispumpstartcountcontrolled.
IftheMixeristimecontrolled,itwillstartindependentofpumpstart.
Inbothcasesminandmaxlevelformixstartmustbeperformed.
Congurethepumpstartdelayinmenu:
Settings / Pump x / Time settings/ Threshold on delay.
Youmustsetthisdelayonthepumpwiththeloweststartlevel.
4.5 Mixeranddrainpumpblocking
Thereisafunctionwhereyoucansetadigitalinputtoblockthemixerordrainpump.Itispossibletosetan
alarmwithfreealarmtextforeachinput.Whenthesignalisactivatedthemixer/drainpumpwillstopandblock.
Ifanalarmisenabled,itwillbecomeactive.
In menu Settings / Digital Inputs / Digital In x
Set Input function to [Mixer block] or [Drain pump block].Inthesamemenusetuseralarmtextandalarm
priority.

Table of Contents