5.3 System settings
Table5-1showsthecompletelistofsystemsettings.
Table 5-1 Systemsettings,underthemenuitem‘Settings>System’
Submenu Submenu Setting Value Passcode Comment
__
Select Language Select a language Operator
Same as the setting described in
Section 5.1
Station Application
Pump Controller
System
Pump Monitor PumpMonitor:SeeSection 3.1
Select Units
(Metricunits,
US units)
System
Metric:m,m
2
,m
3
,Liters/second
(liters/s),bar,mm,ºC
US:ft,ft
2
,gal,GPM(gal/min),
psi,raºF
DateFormat
(YYYY.MM.DD,
DD.MM.YYYY,
MM.DD.YYYY)
System
SetDate Date
System
Set Time Time
LCDBacklight
Timeout
Minutes
Ifyouenteravalueof0,the
backlightwillalwaysbeon.
LevelDisplay
Graphics
m,ft
Hide Start - Stop
Levels
No,Yes
Alarm Alert On Time Minutes
Alarm Alert
Pause Time
Minutes
MainPower3~Voltage Volts Usedassetpointsforsystem
alarms.
MainFrequency Hz
SystemAlarms
Power Fail
AlarmType
(Inactive,
B-Alarm,A-Alarm)
System
AlarmDelay Seconds
Incoming Phase
Missing
AlarmType
(Inactive,
B-Alarm,A-Alarm)
AlarmDelay Seconds
LowSupplyVoltage
AlarmType
(Inactive,
B-Alarm,A-Alarm)
AlarmDelay Seconds
Limit Volts
Hysteresis Volts
NV
ChecksumError
AlarmType
(Inactive,
B-Alarm,A-Alarm)
NV Checksum Error is issued if
thechecksumforthenonvolatile
memoryindicateserror.
AlarmDelay Seconds