3.2 Pumpcapacityandin/outowofthepit
In-/outflow and pump capacity calculation
Function
Calculatestheinowusinglevelchangepertimeunitandsurfacearea.
Calculatesthepumpcapacityeverytimeapumprunsbyitself.
Pumpandsystemdatacanbeenteredforamoreexactcalculation.
Anevenhigherowcalculationaccuracyisobtainedifapressuresensorismountedon
the mains outlet.
Outowcalculationcompensationforrpm.
Outowcanbetakenfromaowmeter.
Value
Servicethepumpbeforebreakdown,avoiding/reducingoverows.
Avoidwastingenergyusingpumpswithdegradede󰀩ciency.
Servicecanbeplannedtooccurduringnormalworkinghours.
Noexternalowmeterrequired.
Accurateoverowmeasurement
The PC 441 supports several approaches to flow calculation and combinations thereof
1. Flowisbasedonmanuallyenteredcapacityvaluesforeachpump.Thisdataisthenusedtotheoretically
calculatethepumpedvolumebymultiplyingcapacitydatawithrunninghours.
Pros: Simpleset-up
Cons: Noactualpumporsystemhealthcheck
2. Flowisbasedonaowmeasuringdevicemountedonthemains.
Pros: Simpleset-upwithaccurateowmeasurementifmountingcriteriaaremet
Cons: Noinformationoninowandcollectionsystembehaviour