5.12 Settings for digital inputs
Table5-10showsthecompletelistofsettingsyoucanmakeunderthesubmenuDigital Inputs.
Table 5-10 Settings for d
igitalinputs,under‘Settings>DigitalInputs’
Submenu Submenu Setting Value Passcode Comment
DigitalInput1
to
DigitalInput12
Input Function
(O FF,
Pumprunindication,
Manuelpumpstart,
Pumpnotinauto,
Startoat,
Pumpfailure,
Motorprotector,
Hightemperature,
Leakage,
StopoatP1-P4,
Lowleveloat,
Overowsensor,
Highleveloat,
Drainpumpoat,
Runind.drainpump,
M.prot.drainpump,
Runindicationmixer,
Motorprot.mixer,
Stainstation
Alarmreset,
Powerfail,
DIpulsechannel1-4
BlockPIDcontroller,
Alarminput,
Mixerblock+Alarm
input,
Drainpumpblock+
Alarm input
Blockremotedata)
System
There is a total of 16 digital (on/
o)inputchannels.Therst12
ones can be chosen from a list
of26functions.However,we
recommendtokeepthedefault
conguration,whichislistedin
the installation Guide.
Pump Not in Autoisusuallya
signal from a manual switch
that disconnects the pump com-
pletelyfrombeingcontrolled
from this unit.
Manual Startmaybeconnected
to a manual switch - its function
will be identical to that of start-
ingthepumpbyusingthemenu.
DigitalInput13
to
DigitalInput16
Input Function
(SameasDigitalIn
1 – 12 above with
additionalfunctions:
InputPulseCh.1,
InputPulseCh.2,
InputPulseCh.3,
InputPulseCh.4,)
System
Thelast4digitalinputchannels,
thatarenumbered13-16,can
be chosen from a list of 29 func-
tions.However,werecommend
tokeepthedefaultcongura-
tion,wheretheyareusedfor
Input Pulse Ch. 1,
Input Pulse Ch. 2,
Input Pulse Ch. 3 and
Input Pulse Ch. 4
respectively.
NormallyState
(NormallyOpen
(NO),
Normally
Closed(NC))