EasyManua.ls Logo

Sulzer ABS PC 441 - Digital Output Type: Data Reg. Setpoint

Default Icon
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81307063I
EN
44
Digital Output 1 Logic IO function
Output Function IO signal 1
[Logic IO] [True OR]
Normaly State IO number 28
[Normaly Open (NO)] IO signal 2
[True OR]
IO number 29
IO signal 3
[True OR]
IO number 30
IO signal 4
Esc
TheresultwillbethatDO1willbeactivatedifanyofthealarmsfortemperaturearetriggered.
4.2 Digital output type: data reg. setpoint
WiththeDigitalOutputType“Data reg. Setpoint”asetpointcanbetiedtoanyanalogsignal,internalorexter-
nal.ByusingtheregistersdenedintheModbusmanualandenteringtheminthefunctionasintheexample
below,youcanachievethisfunction.
Example Wehaveasulphuricgasmonitoringdeviceconnectedtoananaloginputsignal.WeuseA.IN5forthesulphuric
meter.InthiscasewewantaswitchonDO1whentheconcentrationofgasisorabove10.0ppm.Wealso
wanttheoutputsignaltoswitchbackat1.0ppm(ahysteresisof9ppm).Thisdigitaloutput1controlsafan
which evacuates the gas from the station.
NOTE! According to Comli/Modbus reference manual(p/n81307126)wendthattheregisterforanaloginput5istoread
on register 5;seegure4-2below.Wenoteaswellthatthescalefactoris0.1(i.e. the value in reg.5 is multi-
plied by 0.1 to get actual value in engineering units).
Figure 4-2 AbovetableisanextractfromtheComli/ModbusmanualforPC441–
Analog inputs/Output in engineering units.
ThefunctionisconguredinthemenuofCA511asfollows:UnderSettings / Digital outputs / PC 441 Main (or
CA 781 Exp.-) Module / Digital output 1 to [Data reg. setpoint] according to picture below.
Andthentypeinthesetpointvalue100forONstateandthevalue10forOFFstate
Digital Output 1 Digital Output 1
Output Function Data Register
[Data reg. Setpoint] 5
Normaly State Setpoint ON
[Normaly Open (NO)] 100
Setpoint OFF
10
Setpoint Delay
5 s
Esc
The Setpoint ON=100 correspond to the value of 10 engineering units and
Setpoint OFF=10 correspond to 1.
AboveisanexampleofhowtogetananalogsensorsignaltochangestateonaDigital Output signal via Data
reg. setpoint function.

Table of Contents