3.5 Pump reversing
In the Settings / Common P1-P4 / Pump reversingspecieswhichpumporpumpsshallusethereversing
function.
Thereversingcanbetriggeredon:
• Digitalinput“PumpFail”
• Tripped motor protector (after auto reset)
• High motor current
• Lowpumpcapacity
• Preset number of pump starts
If more than the set threshold for number of reverse triggers occurs within a preset time frame (default 5/60
minutes),nofurtherreverseattemptsaredonewithinthesetblocktime(default24h),ifmanualresetnotis
required.AcknowledgeoftheMaxreverseattemptsalarmoramanualreversefromlocalcontrolpanelclears
potentialreverseblockconditions.
Reversing when digital in pump fail active
If set to YES;ReversecyclestartswhendigitalinputsignalPumpFailgoesactive.Thesignalmustgobackto
inactivestatebeforethepumpstartreversing.Ifnotreversingcycleisaborted.
Reversing when Fallen motor-protector
If set to YES;ReversecyclestartswhenthedigitalinputsignalMotorProtectorgoesactive.Motorprotector
will be reset before the pump starts reversing. You must enable auto reset motor protector function for the
pump. Set the cold down time and pulse time in the auto reset menu. If the motor protector reset fails reversing
cycleisaborted.
Reversing when Low pump capacity
If set to YES;Reversecyclestartsonalarmforlowpumpcapacity.Forthisfunctiontoworkyouneedtoen-
ablethelowpumpcapacityalarminthepumpalarmsmenu.Afterreversing,thefunctionisdisableduntila
minimumof10newpumpcapacitiescalculationshavebeencompleted.Whenenablingthepumpcapacity
calculation,theusermustsetthenominalcapacityforthepump:
- In menu Status / Pump X / Pump capacity
Reversing on overcurrent
Reversecyclestartswhenalarmforhighmotorcurrentisactivated.Forthisfunctiontoworkyouneedtoen-
ablethealarminthepumpalarmmenu.Usethealarmdelaytimetodelaythestartofreversing(don’ttrigger
on pump start current).
Reversing on start count
Thereverscyclecanbetriggedafterspeciednumberofstartsforeachpumptoeliminateclogsandensure
proper function. If this function is set to YES,thesubmenuappears,andselectablenumberofstartscanbe
speciedforeachpump.Inthissubmenu,thecurrentstartcountersaredisplayed.
3.5.1 Other settings regarding pump reversing:
In menu Settings / Common P1-P4 / Pump reversing
- Set [Reversing pump x] to [Yes].
- Set [Start rev. delay time].Thetimetoholdthepumpinopositionbeforethestartofpumpreversing
- Set [Rev. run time]. The reversing run time.
- Set [Max no. attempts]Afterthereversing,thepumpwillstartagain.Ifthepumpfailsagain,anewreversing
cyclewillbegin.Hereyousetmaxnumberofattempts.
Pump reverse is considered successful when the pump has been running for the set time [Start rev. delay
time]withoutanypumperror.
On success the attempt counter is reset.
Iftheattemptscounterreachesmaxnumberofattempts,analarmwillbegeneratedandallfurtherreversing
stoppeduntilmotorprotectoralarmorpumpfailalarmshasbeenresetmanually.
- Set [Stop pumps before rev.] to [Yes]ifyouwanttheotherpumpstostopandstayblockedwhenreversing
cyclerun.
If [Pump rel. when rev] is set to [ON],thepumprelaywillbeactivated1secafterthereversingrelayandwill
bedeactivated1secbeforethereversingrelayisdeactivated.Herepumprelayisusedtocontrolthepump
(on/o)andreversingrelayisusedtoshifttwophasesbeforereversing.
If [Pump rel. when rev] is set to [OFF]onlyreversingrelayisactivatedduringreversing.Pumprelayisalways
oduringthereversingprocess.