5.6 Common settings for pump 1, 2, 3 and 4.
Table5-4showsthecompletelistofsettingsyoucanmakeunderthesubmenu Common P1-P4.
Table 5-4
Commonsettingsforpump1,2,3and4,under‘Settings>CommonP1-P4’
Submenu Submenu Setting Value Passcode Comment
Log Pump Events Default:OFF (OFF,ON) System
Auto Reset M. Protect
Reset Protector P1 (NO,YES)
System
Pulse Time is the duration of the
reset pulse.
Pause Time is used for two
purposes:
(1) the cooling time before a new
resetisattempted,
(2) the counter for Max No. At-
tempts is reset when the pump
has been running for Pause Time.
...
...
...
...
Reset Protector P4 (NO,YES)
Pulse Time Seconds
Pause Time Seconds
MaxNo.Attempts Integer
PumpExercising
ExercisePump1 (NO,YES)
System
Thisisusedto“exercise”the
pumpsiftheyhavebeenstanding
still for Max Stand Still Time.
If‘Start if Level >=’islowerthan
‘Start if Level <’,thisisthewindow
wherethepump(s)mayrun.In
theoppositecase,thepump(s)
mayonlyrunoutsidethatwindow.
Whentheconditionismet,the
pump(s) will run for Running Time.
...
...
...
...
ExercisePump4 (NO,YES)
MaxStandStillTime Minutes
Running Time Seconds
StartifLevel>= m,ft
StartifLevel<= m,ft
Pump Reversing
Reversing Pump 1 (NO,YES)
System
This is used to reverse the pump
when a pump failure has occurred.
The start of the reversing can
betriggedbythemotorprotec-
tor or the digital input (pump fail)
orwhenlowpumpcapacityis
detected.
If Pump Relay When Rev. is set
to ONthepumprelaywillbeacti-
vated one second after the revers-
ingrelayandgoeso󰀨onesecond
beforethereversingrelay.
...
...
...
...
Reversing Pump 4 (NO,YES)
Rev. On Pump Fail (NO,YES)
Rev. On Fallen M. prot (NO,YES)
Rev. On Low P. Cap (NO,YES)
Rev. On Overcurrent (NO,YES)
StartRev.DelayTime MInutes
Rev. Running Time Seconds
MaxNo.Attempts Integer
PumpRelay
WhenRev.
(OFF,ON)
Stop Pumps
Before Rev.
(NO,YES)
PowerPumpBlocking
On Over Voltage (NO,YES)
System
Usealarmlimitsfromthesystem
alarms menu.
On Under Voltage (NO,YES)
On Unbalanced
Voltage
(NO,YES)
OnHighFrequency (NO,YES)
OnLowFrequency (NO,YES)
BlockOnDelay Seconds
BlockO󰀨Delay Seconds