5.10 Cleaner
Table5-8showsthecompletelistofsettingsyoucanmakeunderthesubmenuCleaner.
Table 5-8 Cleaner,under‘Settings>Cleaner’
Submenu Submenu Setting Value Passcode Comment
- Flushat:
(PumpStart,
Pump Stop)
System
- Flushing Time Seconds
- No.StarttoFlush Integer
5.11 Analog logging
Table5-9showsthecompletelistofsettingsyoucanmakeunderthesubmenuAnalog Logging.
Table 5-9 Analoglogging,under‘Settings>AnalogLogging’
Submenu Submenu Setting Value Passcode Comment
Log Channel 1 to Log Channel 16
Log Signal
(Closed,
PitLevel,
PitInow,
PitOutow,
OverowLevel,
OverowFlow,
Back-Pressure,
MotorCurrent,
PumpCapacity,
PowerFactor,
Temp.Stator,
Temp.UpperBearing,
Temp.LowerBearing,
Vibrations,
MainVoltage,
MainFrequency,
FreeChoice,
SupplyVoltage,
PulseChannel,
Temperature Stator
WiringL2,
Temperature Stator
WiringL3,
PidControlleroutput,
DataRegister,
DataRegister
(2-compl.),
ActualVFDfrequency
P1-P4,
TotalHead,
Actual Head)
System
A total of 16 analog channels
whoseoutputsyoucanchoose
from the list.
Pulse Channelareusedforrain,
owandenergyvalues.
Temperaturesignalsareonly
meaningfulifyouusePT100
sensors.
Forsomesignalsyouhaveto
choose pump number or pulse
channel.
Log Function
(Closed,
ActualValue,
AverageValue,
MinValue,
MaxValue)
Log Interval Minutes