96
11.2.2 Charge Temperature Derating
figure 11-4 Charge temperature derating curve of SC1200UD-US/SC1375UD-US/SC1575UD-US/
SC1725UD-US/SC2000UD-US
Ambient temp. T PCS operation situation
T<-35 The PCS starts with the aid of auxiliary heater
-35<T≤45 Operate for a long time at 100% of the overload condition
45<T≤50 Operate with derating at 1.82%
50<T≤60 Operate with derating at 9.09%
T>60 Enter protection mode;
figure 11-5 Discharge temperature derating curve of SC2500UD
Ambient temp. T PCS operation situation
T<-35 The PCS starts with the aid of auxiliary heater
-35<T≤40 Operate for a long time at 100% of the overload condition
40<T≤50 Operate with derating at 1%
50<T≤60 Operate with derating at 9%
T>60 Enter protection mode;
Note: SC2500UD and DCDC form a two-level system application, and the working DC bus
voltage range is [1300 ~ 1360]V.