125
Parameter SC1200UD-US SC1375UD-US
Compliance
UL1741, UL1741 SA, IEEE 1547, Rule 21, HECO
14H, CSA C22.2 No.107.1-01
Grid support
L/HVRT,L/HFRT, active & reactive power control
and power ramp rate control, Volt-var, Volt-watt,
Frequency-watt
table 16-2 SC1575UD-US&SC1725UD-US
Parameter SC1575UD-US SC1725UD-US
DC side parameter
Max. DC voltage
1500 V
Min. DC voltage
915 V 1000 V
Working voltage range
915 – 1500 V 1000 – 1500 V
Max. DC current 1760A
No. of DC inputs
1 or 10
②
AC side(Grid)
AC output power
1732 kVA @ 30 ℃
(86℉) / 1575 kVA @ 45
℃ (113 ℉)
1897 kVA @ 30 ℃
(86℉) / 1725 kVA @ 45
℃ (113 ℉)
Max. AC current
1587 A @ 30 ℃ (86℉) / 1443 A @ 45 ℃ (113 ℉)
Nominal AC voltage
630 V 690 V
AC voltage range
554 – 693 V 607 – 759 V
Nominal grid frequency / Grid fre-
quency range
60 Hz / 55 – 65 Hz
Max. THD of current
< 3 % (at nominal power)
DC component
< 0.5 % In
Power factor at nominal power / Ad-
justable power factor
0.99 / 1 leading - 1 lagging
Adjustable Reactive power
-100 % – 100 %
Feed-in phases / Connection
phases
3 / 3
AC side (Off-Grid)
Nominal AC voltage
630 V 690 V
User Manual 16 Appendix