7 iSolarCloud App User Manual
Parameter
Definition/Setting Descrip
tion
Range
Active power rising gradi
ent
The rise rate of inverter active
power per minute.
3%/min~6000%/min
Active power setting per
sistence
Switch for enabling/disabling
the function of saving output
limited power.
Enable/Disable
Active power limit The switch for limiting output
power.
Enable/Disable
Active power limit ratio The ratio of limiting output pow
er to rated power in percentage.
0%~110%
Shutdown when active
power limit to 0%
Switch used to determine
whether the inverter is in stop
state when the limited power
reaches 0.
Enable/Disable
Reactive Power Regulation
Tap Settings > Power Regulation Parameters > Reactive Power Regulation to enter the
screen, as shown in the following figure.
figure 7-18 Reactive Power Regulation
table 7-9 Reactive Power Regulation
Parameter
Definition/Setting Descrip
tion
Range
Reactive power genera
tion at night
Switch for enabling/disabling Q
at night function.
Enable/Disable
Reactive power ratio at
night
Reactive power ratio set for the
Q at night function.
-100%~0%/
0%~100%