User Manual 7 iSolarCloud App
figure 7-16 NS Protection(Passive Valid)
7.8.3 Power Regulation Parameters
Active Power Regulation
Tap Settings > Power Regulation Parameters > Active Power Regulation to enter the
screen, as shown in the following figure.
figure 7-17 Active Power Regulation
table 7-8 Active Power Regulation
Parameter
Definition/Setting Descrip
tion
Range
Active power soft start af
ter fault
The switch for enabling/dis
abling the soft start function af
ter a fault occurs.
Enable/Disable
Active power soft start
time after fault
Time that the soft start takes to
raise the power from 0 to 100%
rated power.
1s~1200s
Active power gradient
control
Switch for enabling/disabling
the active power rate settable
function.
Enable/Disable
Active power decline gra
dient
The decline rate of inverter ac
tive power per minute.
3%/min~6000%/min