87
Parameter
Definition/Setting
Description
Range
Active power gradient
control
Switch for enabling/disabling
the active power rate settable
function.
Enable/Disable
Active power decline
gradient
The decline rate of inverter ac-
tive power per minute.
1%/min~6000%/min
Active power rising
gradient
The rise rate of inverter active
power per minute.
1%/min~6000%/min
Active power setting
persistence
Switch for enabling/disabling
the function of saving output
limited power.
Enable/Disable
Active power limit
The switch for limiting output
power.
Enable/Disable
Active power limit ratio
The ratio of limiting output
power to rated power in
percentage.
0%~110%
Shutdown when active
power limit to 0%
Switch used to determine
whether the inverter is in stop
state when the limited power
reaches 0.
Enable/Disable
Active Overload
Switch
Switch used to ensure that the
inverter operates at the maxi-
mum active power when PV
power limit ratio is set over
100%.
Enable/Disable
Reactive Power Regulation
Tap “Settings→Power Regulation Parameters→Reactive Power Regulation” to enter
the screen, as shown in the following figure.
User Manual 7 iSolarCloud App