FFiigguurree 77--1166 Active Power Regulation
Table 7-8 Description of Active Power Regulation Parameters
PPaarraammeetteerr
DDeessccrriippttiioonn RRaannggee
Active Power Soft Start
after Fault
Switch for activating/deactivating the
function of active power soft start after a
fault occurs
On/Off
Active Power Soft Start
Time after Fault
The soft start time required for raising active
power from 0 to rated value after a fault
occurs
1 s–1200
s
Active Power Gradient
Control
Set whether to enable active power gradient
control
On/Off
Active Power Decline
Gradient
Decline gradient of inverter active power per
minute
3 %/min–
6000
%/min
Active Power Rising
Gradient
Rising gradient of inverter active power per
minute
Active Power Setting
Persistence
Switch for activating/deactivating the
function of active power setting persistence
On/Off
Active Power Limit
Switch for limiting active power
On/Off
Active Power Limit Ratio
The ratio of active power limit to rated power
in percentage
0.0 %–
110.0 %
DRM
Switch for activating/deactivating the DRM
function
On/Off
RReeaaccttiivvee PPoowweerr RReegguullaattiioonn
Tap SSeettttiinnggss→→PPoowweerr RReegguullaattiioonn PPaarraammeetteerrss→→RReeaaccttiivvee PPoowweerr RReegguullaattiioonn to enter
the screen, as shown in the following figure.