25
5 Mechanical Mounting
5.1 Safety and Location Requirements
In order to avoid electric shock or other injury, be sure there is no electricity
or plumbing installations before drilling holes.
Risk of injury due to improper handling
y The weight can cause injuries, serious wounds, or bruise.
y Always follow the instructions when moving and positioning the inverter.
System performance loss due to bad ventilation
The inverter requires good ventilation during operation. Keep it upright and
nothing covering the heat sink.
Wear gloves to avoid scratches when mounting the inverter.
The inverter with IP65 can be installed indoors or outdoors.
Selecting an optimal location for the inverter is critical for its operating safety as well
as the expected efficiency and service life. Considerations for the location include:
1. The concrete wall should be suitable for the weight and dimensions of the
inverter.
2. Install the inverter where it is convenient for installation, cable connection
and service.
3. The location should be not accessible to children.
4. The max. power output will reduce when the ambient temperature exceeds
45°C. The following figure shows the ambient temperature and relative
humidity limits.