Factory-Set Values
The parameter values initially set at the factory are shown in Table I.
Table I. Parameter Factory Settings
<aid> Parameter Setting
TS3100 FREQ=5MHz
TOD=NONE
ALMCOND=ALW
IPNE=0.0.0.0
IPSUBNET=255.255.255.255
IPGATE=0.0.0.0
IPEM1=0.0.0.0
IPEM1PORT=0
IPEM2=0.0.0.0
IPEM2PORT=0
IPINACT=0
DCDPASSTHRU=INH DCDUSERPORT=2
BYPASS=ALW (990-72020-04 systems
only)
TS3100 HOLDOVER
ALARM
TIME=24-0
SEV1=EV
SEV2=MJ
SAFF1=NSA
SAFF2=SA
TS3100 GPS
ALARM
TIME=3-0
SEV1=EV
SEV2=MN
SAFF1=NSA
SAFF2=NSA
GPS ANTCBLDLY=0
ANTELEVMASK=10
RO-A, RO-B ENSEMBLER=INH
MONITOR=INH
SPAN-A, SPAN-B ENSEMBLER=INH
MONITOR=INHSSM=INH
SSM=INH
SIGNAL=DIGITAL
SSMCHANNEL=4