158 TimeSource 3100
TL1 Reference
097-72020-01 Issue 9: November 2003
Retrieve Equipment (cont’d)
Response Format:
<sid> <date> <time>
M <ctag> COMPLD
"<aid>::::<spec_block>"...
/*LINK:<link>,CMD:<command>*/
;
The parameters which may be displayed in the <spec_block> are listed below.
Aid Parameter Value Parameter Description
ALL MONITOR=a a = ALW Monitor is used for alarm purposes
a = INH Monitor is not used for alarm purposes
TS3100 BYPASS=a
(990-72020-04
Systems only)
a = ALW or
INH
During holdover, the traffic-bearing E1 spans on
the ESCIU module pass through the
TimeSource 3100 without being re-timed (ALW)
or the E1 spans continue to be re-timed (INH)
FREQ=a a=5 Frequency for both remote oscillator inputs is 5
MHz
a=10 Frequency for both remote oscillator inputs is
10 MHz
TOD=a a=CISCO Serial message sent is Cisco format
a=NTP4 Serial message sent is NTP Type 4 format
a=NONE No serial message is sent
ALMCOND=a a=ALW Alarm conditioning for outputs is enabled
a=INH Alarm conditioning for outputs is disabled