Chapter 8 Communication Functions
8-56
After the frame setting and BCC setting completes, click the OK button.
You can see the frame list window which is designated as below
Program
When the data is received at frame no. 0, link relay L000 turns on during 1 scan. At that moment P004 increases and
the value of P004 moves M000.
The new value of P004 is sending again every 1 second period (F092 is 1second period flag)
The number of sending normally is stored in D000.
When error occurs the number of sending error is stored in D001.