Chapter 10 Maintenance
10-2
10.3 Periodic Inspection
Check the following items once or twice every six months, and perform the needed corrective actions.
Check Items Checking Methods Judgment Corrective Actions
Ambient
temperature
0 ~ 55 °C
Ambient Humidity 5 ~ 95%RH
Ambient
Environment
Ambience
-. Measure with thermometer and
hygrometer
-. measure corrosive gas
There should be no
corrosive gases
Adjust to general standard
(Internal environmental standard of
control section)
Looseness, Ingress
The module should be move
the unit
The module should be
mounted securely.
PLC
Conditions
dust or foreign
material
Visual check No dust or foreign material
Retighten screws
Loose terminal
screws
Re-tighten screws Screws should not be loose Retighten
Distance between
terminals
Visual check Proper clearance Correct
Connecting
conditions
Loose connectors Visual check
Connectors should not be
loose.
Retighten connector mounting
screws
Line voltage check
Measure voltage between input
terminals
*85 ~ 264V AC
*20~28V DC
Change supply power
Fuse Visual check No melting disconnection
If fuse melting disconnection,
change the fuse periodically
because a surge current can cause
heat

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the T-solution MASTER-K120S and is the answer not in the manual?

T-solution MASTER-K120S Specifications

General IconGeneral
BrandT-solution
ModelMASTER-K120S
CategoryController
LanguageEnglish

Related product manuals