Chapter 6 Input and Output Specification
6-12
Expansion Module
Model
Specifications
G7E-TR10A
Output point 10 points
Insulation method Photo coupler insulation
Rated load Voltage/current DC12V/24V
Operating load voltage range DC10.2 ~ 26.4V
Max. load current 0.5A/1 point, 4A/1COM
Current leakage when off 0.1mA or lower
Max. inrush current 4A/10ms or lower
Max. Voltage drop when on DC 1.5V or lower
Surge Absorber Clamp diode
Off On 2 ms or lower
Response time
On Off 2 ms or lower
Common method 10 points/ 1COM,
Operation indication LED is on at on status of output
REMARK
1) Refer to 7.2 ‘Special Functions’ for the special modules