4.10.8 Auxiliary Commands
BOOL <DSC>
Function Select query Return format of Boolean (<Bool>) commands.
DIGIT – Boolean queries are replied with 0|1.
TEXT Boolean queries are replied with OFF|ON.
Parameters
DIGIT|TEXT, 0|1
Query
BOOL?
Returns
<DSC> DIGIT|TEXT
NOTE
BOOL <DSC> command is available from firmware revision 02.110.
LANG <DSC>
Function
Sets the communication protocol to SCPI language.
Parameter
SCPI
RIE <Bool>
Function Enable / Disable ILC function. If disabled, power supply ignores the ILC pin
state.
Parameters
0|1, OFF|ON
Query
RIE?
Returns
<Bool> 0|1
PVS <DSC>
Function Set the Voltage programming source: Front Panel, External Resistor, or
External Voltage.
Parameters
0|1|2 or DIG|VOL|RES
Query
PVS?
Returns
<DSC> DIG|VOL|RES
PCS <DSC>
Function Set the Current programming source: Front Panel, External Resistor, or External
Voltage.
Parameters
0|1|2 or DIG|VOL|RES
Query
PCS?
Returns
<DSC> DIG|VOL|RES