If it can be proven that guidelines were not observed, or installation was carried
liability for the malfunctions experienced and any further claims that may arise
thereof.
All cables used must be fuel-resistant.
For cabling in an area that is not
intrinsically safe, explosion-grade
cable must be used! For wiring the
battery supply and the internal
CAN bus the enclosed instructions
part no. NM2KABEL only may be used.
All cables must be laid (protected) in
such a way that they are not damaged,
nor the operators injured, as a result of
normal operation and use.
Please lay a separate supply cable from the voltage source.
The cable need not be shielded.
Protect the system with an 8 A fuse.
Obtain the +24V voltage through a secured cable directly from the battery’s plus
pole.
Use this voltage supply only for the device/system.
supply line only.
The 0V line must not be switched.
Never supply the printer with external voltage.
EXPLOSION HAZARD
Any kind of manipulation, either mechanical or electrical, is prohibited!
MultiLevel Instruction Manual Installation
Installed devices in the Tank Truck