MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 73 Thomson Technology
Control
This setup menu consists of the synchronization setup and the regulation setup.
Synchronization
2010 Synchronization type
No. Setting First setting Second
setting
Factory
setting
2011 Sync. type Sync. type Static sync. Dynamic
sync.
Dynamic
sync.
If dynamic synchronization is chosen, the next menu will be
2020 Dynamic Synchronization
. If
static synchronization is chosen, the next menu will be
2030 Static Synchronization
.
2020 Dynamic Synchronization
No. Setting Min. setting Max. setting
Factory
setting
2021 Dynamic sync. df max. 0.0Hz 0.5Hz 0.3Hz
2022 Dynamic sync. df min. -0.5Hz 0.5Hz 0.0Hz
2023 Dynamic sync. dU max. 2% 10% 5%
2024 Dynamic sync. Breaker delay 40 ms 300 ms 50 ms
2030 Static Synchronization
No. Setting Min. setting Max. setting
Factory
setting
2031 Static sync. Maximum df 0.00Hz 0.50Hz 0.10Hz
2032 Static sync. Maximum dU 2% 10% 5%
2033 Static sync. Close window 0.1 deg. 20.0 deg. 10.0 deg.
2034 Static sync. Phase K
P
0 1000 10
2035 Static sync. Phase K
I
0 1000 10
2040 Sync. blackout
No. Setting Min. setting Max. setting Factory
setting
2041
Sync. blackout df max. 0.0Hz 5.0Hz 3.0Hz
2042
Sync. blackout dU max. 2% 10% 5%
Settings are accepted limits (generator voltage and frequency) for closing the generator and
mains breaker. The values are according to nominal values.
Example:
f
NOM
and U
NOM
= 50 Hertz and 400 volts.
With factory settings the breaker is able to close, if the frequency is between 47 and 53 Hertz
and the voltage is between 380 and 420 volts.