6310 Idle running
No. Setting Min. setting Max. setting
Factory
setting
6311 Idle running Start timer 0.0 min 999.9 min 300.0 min
6312 Idle running Enable start timer OFF ON OFF
6313 Idle running Stop timer 0.0 min 999.9 min 300.0 min
6314 Idle running Enable stop timer OFF ON OFF
6315 Idle running Idle relay Option dependent R0 (none)
6316 Idle running Enable OFF ON OFF
6400 Master clock
No. Setting Min. setting Max. setting
Factory
setting
6401 Master clock Start hour 0 23 8
6402 Master clock Stop hour 0 23 8
6403 Master clock Difference 0.1Hz 1.0Hz 0.1Hz
6404 Master clock Set point 1 s 999 s 20 s
6405 Master clock Enable OFF ON OFF
6410 Battery test
No. Setting Min. setting Max. setting
Factory
setting
6411 Battery test Set point 8.0V DC 32.0V DC 18.0V DC
6412 Battery test Delay 1 s 300 s 20 s
6413 Battery test Output A R0 (none)
6414 Battery test Output B
Option dependent
R0 (none)
6415 Battery test Enable OFF ON OFF
6420 Voltage trip
No. Setting Min. setting Max. setting Factory
setting
6421 Voltage trip Type Phase-phase
Phase-neutral
Phase-phase

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON MEC 320 - GENSET CONTROLLER and is the answer not in the manual?

THOMSON MEC 320 - GENSET CONTROLLER Specifications

General IconGeneral
BrandTHOMSON
ModelMEC 320 - GENSET CONTROLLER
CategoryController
LanguageEnglish

Related product manuals