PM079 Rev 0 07/06/08 92 Thomson Technology
6590 Mains failure voltage
No. Setting Min. setting Max. setting
Factory
setting
6591 Mains failure U Fail. delay 1.0 s 990.0 s 5.0 s
6592 Mains failure U Mains OK delay 10 s 9900 s 60 s
6593 Mains failure U Low voltage 80% 100% 90%
6594 Mains failure U High voltage 100% 120% 110%
6595 Mains failure U Mains fail. control
Start eng. +
open MB
Start eng. Start eng. +
open MB
6600 Mains failure frequency
No. Setting Min. setting Max. setting Factory
setting
6601
Mains failure f Fail. delay 1.0 s 990.0 s 5.0 s
6602
Mains failure f Mains OK delay 10 s 9900 s 60 s
6603
Mains failure f Low frequency 80.0% 100.0% 95.0%
6604
Mains failure f High frequency 100.0% 120.0% 105.0%
6610 Mains breaker control
No. Setting Min. setting Max. setting Factory
setting
6611
MB control Function Mode shift
OFF
Mode-AMF-
Mode
Mode shift
OFF
6612
MB control Timer t
MBC
0.0 s 30.0 s 0.5 s
6613
MB control Back synchroni-
sation
OFF ON OFF
6614
MB control Sync. to mains OFF ON ON