MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 75 Thomson Technology
2120 Breaker sequence
No. Setting Min. setting Max. setting
Factory
setting
2121 Breaker seq. Break Close GB Close GB+TB
Close GB
2122 Breaker seq. Timer 0.0 s 999.0 s 5.0 s
2123 Breaker seq. Run 90 0 RPM 4000 RPM 1450 RPM
2130 Excitation failure
No. Setting Min. setting Max. setting
Factory
setting
2131 Excit. failure Timer 0.0 s 999.0 s 5.0 s
2132 Excit. failure Relay output A R0 (none) R0 (none)
2133 Excit. failure Relay output B R0 (none)
Option
dependent
R0 (none)
2134 Excit. failure Enable OFF ON OFF
2135 Excit. failure Fail class Alarm (1) Trip MB (6) Warning (2)