MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 82 Thomson Technology
4200 VDO 105.2
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4201
VDO 105.2 Set point 40 deg. 150 deg. - 110 deg.
4202
VDO 105.2 Timer 0.0 s 100.0 s - 5.0 s
4203
VDO 105.2 Relay output A
R0 (none) - R0 (none)
4204
VDO 105.2 Relay output B
R0 (none)
Option
dependent
- R0 (none)
4205
VDO 105.2 Enable OFF ON RUN OFF
4206
VDO 105.2 Fail class Alarm (1) Trip MB (6) - Trip/stop (4)
4210 VDO 106.1
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4211
VDO 106.1 Set point 0% 100% - 10%
4212
VDO 106.1 Timer 0.0 s 100.0 s - 10.0 s
4213
VDO 106.1 Relay output A R0 (none) - R0 (none)
4214
VDO 106.1 Relay output B R0 (none)
Option
dependent
- R0 (none)
4215
VDO 106.1 Enable OFF ON RUN OFF
4216
VDO 106.1 Fail class Alarm (1) Trip MB (6) - Warning (2)
4220 VDO 106.2
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4221
VDO 106.2 Set point 0% 100% - 5%
4222
VDO 106.2 Timer 0.0 s 100.0 s - 10.0 s
4223
VDO 106.2 Relay output A R0 (none) - R0 (none)
4224
VDO 106.2 Relay output B R0 (none)
Option
dependent
- R0 (none)
4225
VDO 106.2 Enable OFF ON RUN OFF
4226
VDO 106.2 Fail class Alarm (1) Trip MB (6) - Trip/stop (4)
4300 Running detection
This set point is used to define the level where the gen-set is recognised as running. When this
RPM level is reached, the automatic running detection is enabled
(6150 Running status)
.
Also take notice of the menu ‘remove starter’ set point
(6160 Remove starter)
.
No. Setting Min. setting Max. setting
Factory
setting
4301
Running detection Set point 1 RPM 4000 RPM 1000 RPM
4302
Running detection Type Frequency detection X
Running detection Type Tacho
Running detection Type Binary input
Running detection Type Engine I/F communication
4310 Overspeed 1
No. Setting Min. setting Max. setting Factory
setting
4311
Overspeed 1 Set point 1 RPM 4000 RPM 1450 RPM
4312
Overspeed 1 Timer 0.0 s 100.0 s 5.0 s
4313
Overspeed 1 Relay output A R0 (none) R0 (none)
4314
Overspeed 1 Relay output B R0 (none)
Option
dependent
R0 (none)
4315
Overspeed 1 Enable OFF ON OFF
4316
Overspeed 1 Fail class Alarm (1) Trip MB (6) Warning (2)