MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 77 Thomson Technology
2640 Relay control
No. Setting Min. setting Max. setting Factory
setting
2641
Relay control GOV ON time 10 ms 3000 ms 500 ms
2642
Relay control GOV per. time 50 ms 15000 ms 2500 ms
2690 Delay regulation
No. Setting Min. setting Max. setting Factory
setting
2691
Delay regulation Timer 0 s 9900 s 0 s
2692
Delay regulation Output A R0 (none) R0 (none)
2693
Delay regulation Output B R0 (none)
Option
dependent
R0 (none)
2694
Delay regulation Enable OFF ON OFF
2700 Short time paralleling
No. Setting Min. setting Max. setting Factory
setting
2701
Short paralleling Enable OFF ON OFF
2702
Short paralleling Timer 0.10 s 99.90 s 0.30 s

Table of Contents