MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 83 Thomson Technology
4320 Overspeed 2
No. Setting Min. setting Max. setting Factory
setting
4321
Overspeed 2 Set point 1 RPM 4000 RPM 1750 RPM
4322
Overspeed 2 Timer 0.0 s 100.0 s 1.0 s
4323
Overspeed 2 Relay output A R0 (none) R0 (none)
4324
Overspeed 2 Relay output B R0 (none)
Option
dependent
R0 (none)
4325
Overspeed 2 Enable OFF ON OFF
4326
Overspeed 2 Fail class Alarm (1) Trip MB (6) Shutdown (5)
4370 Wire failure analogue input 98
No. Setting Min. setting Max. setting Factory
setting
4371
W. fail. ana. 98 Output A R0 (none) R0 (none)
4372
W. fail. ana. 98 Output B R0 (none)
Option
dependent
R0 (none)
4373
W. fail. ana. 98 Enable OFF ON OFF
4374
W. fail. ana. 98 Fail class Alarm (1) Trip MB (6) Warning (2)
4380 Wire failure analogue input 100
No. Setting Min. setting Max. setting Factory
setting
4381
W. fail. ana. 100 Output A R0 (none) R0 (none)
4382
W. fail. ana. 100 Output B R0 (none)
Option
dependent
R0 (none)
4383
W. fail. ana. 100 Enable OFF ON OFF
4384
W. fail. ana. 100 Fail class Alarm (1) Trip MB (6) Warning (2)
4390 Wire failure analogue input 102
No. Setting Min. setting Max. setting Factory
setting
4391
W. fail. ana. 102 Output A R0 (none) R0 (none)
4392
W. fail. ana. 102 Output B R0 (none)
Option
dependent
R0 (none)
4393
W. fail. ana. 102 Enable OFF ON OFF
4394
W. fail. ana. 102 Fail class Alarm (1) Trip MB (6) Warning (2)
4410 Wire failure VDO input 104
No. Setting Min. setting Max. setting Factory
setting
4411
W. fail. VDO 104
Max. 60% 100% 100%
4412
W. fail. VDO 104
Min. 0% 40% 0%
4413
W. fail. VDO 104
Output A R0 (none) R0 (none)
4414
W. fail. VDO 104
Output B R0 (none)
Option
dependent
R0 (none)
4415
W. fail. VDO 104
Enable OFF ON OFF
4416
W. fail. VDO 104
Fail class Alarm (1) Trip MB (6) Warning (2)
4420 Wire failure VDO input 105
No. Setting Min. setting Max. setting Factory
setting
4421
W. fail. VDO 105
Max. 60% 100% 100%
4422
W. fail. VDO 105
Min. 0% 40% 0%
4423
W. fail. VDO 105
Output A R0 (none) R0 (none)
4424
W. fail. VDO 105
Output B R0 (none)
Option
dependent
R0 (none)
4425
W. fail. VDO 105
Enable OFF ON OFF
4426
W. fail. VDO 105
Fail class Alarm (1) Trip MB (6) Warning (2)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON MEC 320 - GENSET CONTROLLER and is the answer not in the manual?

THOMSON MEC 320 - GENSET CONTROLLER Specifications

General IconGeneral
BrandTHOMSON
ModelMEC 320 - GENSET CONTROLLER
CategoryController
LanguageEnglish

Related product manuals