15.2. VM-3240E VM Extension Amplifier
120 V AC, 60 Hz
690 VA (at rated output), 260 W (according to UL60065), 63 W (at no signal)
240 W, 21 Ω (according to UL60065)
200 W, 25 Ω (according to UL2572)
200 W, 25 Ω (according to CAN/ULC-S576 with separate UPS)
100 W, 50 Ω (according to CAN/ULC-S576)
(Total of Speaker output 1 – 6 Direct Output)
50 Hz – 20 kHz, ±3 dB (at 1/3 rated output), 800 Hz – 2.8 kHz (according to UL2572)
400 Hz – 4 kHz (according to CAN/ULC-S576)
0.7% or less (at rated output, 1 kHz)
85 dB or more
External amplifier Input: 70 V line, removable terminal block (14 pins)
Local Input: –50 dB* (MIC) / –10 dB* (LINE) (changeable), 600 Ω,
electronically balanced, removable terminal block (14 pins)
Speaker output 1 – 2: Max. (240 W) per output
Speaker output 3 – 6: Max. (100 W) per output
Speaker output 2 – 6: Total within rated output, removable terminal block (14 pins)
Allowable minimum load: 245 Ω (20 W) at 70 V line for speaker line failure
detection
Direct output: Direct output from internal or external amplifier,
removable terminal block (16 pins)
Input: Connecting the VM-3240VA
RJ45 female connector
Output: Connecting the VM-3240E
RJ45 female connector
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Input 1 – 8: No-Voltage make contact input, open voltage: 24 V DC,
short-circuit current: 2 mA or less, removable terminal block (14 pins)
Output 1 – 8: Isolated open collector output, withstand voltage: 30 V DC,
operating current: 10 mA or less, removable terminal block (14 pins)
Input 1 – 5: No-Voltage make contact input, open voltage: 24 V DC,
short-circuit current: 2 mA or less, RJ45 female connector
Input 6: Isolated voltage input, Inactive: –24 V ±20%, Active: +24 V ±20%,
RJ45 female connector
Status out: Relay contact output, withstand voltage: 40 V DC,
operating current: 2 – 300 mA, RJ45 female connector
Power in: Connecting the VX-2000DS only (operating range: 20 – 40 V DC)
PS out: 28 V DC / 18 A
M4 screw terminal, distance between barriers: 11 mm
22 V DC Special Application, Maximum feeding current 0.3 A (for RM-200M only)
Connecting the VX-2000DS, RJ45 female connector
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
0 to 49°C (32 to 120°F)
5% to 95% RH (no condensation)
Panel: Aluminum, hair-line, black
Case: Surface-treated steel plate, black, paint
482 (w) x 132.6 (h) x 407 (d) mm (18.98" x 5.22" x 16.02")
16.5 kg (36.38 lb)
Power Source
Power Consumption
Rated Output
Frequency Response
Distortion
S/N Ratio
Input
Output
VM Link
General Control
Emergency Control
Power Input/Output
22 V DC Output
DS Link
Operating Temperature
Operating Humidity
Finish
Dimensions
Weight
AC power cord (2 m) ......................................... 1
Plastic foot ............................................................ 4
Plastic foot mounting screw ................................. 4
Removable terminal plug (14 pins) ...................... 3
Removable terminal plug (16 pins) ...................... 1
Link cable (3 m) ................................................. 1
Note: The design and specifications are subject to change without notice for improvement.
• Accessories

Table of Contents

Other manuals for Toa RM-200M

Related product manuals