69
10.8.2. BGM setting items
[BGM selection]
Select BGM 1 or 2. Press the OK key to confirm the selected BGM output and commence BGM broadcasting.
(For details, refer to "BGM Broadcasts" in "Making General Broadcasts" on page 18.)
BGM 1, BGM 2 and OFF (default)
Setting range
[Treble settings]
Perform treble settings.
+10 dB to –10 dB (Default: 00)
Setting range
[Bass settings]
Perform bass settings.
+10 dB to –10 dB (Default: 00)
Setting range
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in
the Standard for Control and Communication Units for Mass Notification Systems, UL 2572 and CAN/ULC-S576,
certain programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or option
Time / Interval setting
Surveillance group setting
Possible settings
Settings permitted in UL 2572
and CAN/ULC-S576
*
1
Off when no speaker is connected to the VM-3240VA or VM-3240E.
*
2
Off when no VM-3240VA or VM-3240E is connected to the VX-2000DS through DS LINK.
Permitted in UL 2572 and
CAN/ULC-S576
Battery Time
Disable / 00:00 − 23:00
DisabledN
VM-300VA On / Off OnY
External ATT/AC Time-
mains failure status
Time 00:00
Interval 100 sec
Y
Disable / 00:00 − 23:00
Emergency Control Input
Y On / Off
Emergency EV Y On / Off On
VM-3000E Y On / Off On
Battery Y On / Off On
Speaker (Open/Short) Y On / Off
On*
1
Speaker (Earth Fault) Y On / Off On
Charging Equipment Y On / Off
On*
2
General RM Y On / Off
On
On