Greensmaster 3300/3400 Page 6 -- 45 Electrical System
CAN--bus Termination Resistors
Systemcommunicationbetweenelectricalcomponents
onGreensmaster TriFlex machinesis accomplishedon
a CAN--bus communication system. Two (2) specially
designed, twisted cables form the bus for the electrical
system. These wires provide the data pathways be-
tween machine components. At the ends of the twisted
pair of bus cables are 120 ohm termination resistors.
Theresistorsplugintothewireharnessnearthehydrau-
lic lift control manifold under the right side cover next to
the operator seat.
NOTE: Refer to the Electrical Schematics and Wire
HarnessDrawingsinChapter10 --FoldoutDrawingsfor
additional information on termination resistor locations
and wire connections.
Resistor Test
The termination resistors (Fig. 58) can be individually
tested using a digital multimeter (ohms setting). There
should be 120 ohms resistance between terminals A
and B. Terminal C is not used on Greensmaster Tr iFlex
machines.
Figure 58
Termination
A
B
C
Resistor
Electrical
System