[196] Fire Mode The frequency converter is operating in Fire Mode. See parameter
group24-0*
Fire Mode
.
[197] Fire Mode was act. The frequency converter has been operating in Fire Mode, but is now
back in normal operation.
[198] Drive Bypass To be used as signal for activating an external electromechanical bypass
switching the motor direct on line. See 24-1*
Drive Bypass
.
WARNING
If enabling the Drive Bypass Function, the frequency converter is no longer
Safety Certified (for using the Safe Stop in versions where included).
The below setting options are all related to the Cascade Controller.
Wiring diagrams and settings for parameter, see group 25-** for more details.
[200] Full Capacity All pumps running and at full speed
[201] Pump1 Running One or more of the pumps controlled by the Cascade Controller are run-
ning. The function will also depend on the setting of in par.PC-06
Number
of Pumps. If set to
No
[0] Pump 1 refers to the pump controlled by relay
RELAY1 etc. If set to
Yes
[1] Pump 1 refers to the pump controlled by the
frequency converter only (without any of the build in relays involved) and
Pump 2 to the pump controlled by the relay RELAY1. See below table:
[202] Pump2 Running See [201]
[203] Pump3 Running See [201]
Setting in Par. 5-3*
Setting in par.PC-06 Number of Pumps
[0] No [1] Yes
[200] Pump 1 Running Controlled by RELAY1 Frequency Converter controlled
[201] Pump 2 Running Controlled by RELAY2 Controlled by RELAY1
[203] Pump 3 Running Controlled by RELAY3 Controlled by RELAY2
5-30 Terminal 27 Digital Output
Same options and functions as par. 5-3*.
Option: Function:
[0] * No operation
Parameter Description
102 TR200 Programming Guide