EXAMPLE 1:
Variable value= OUTPUT FREQUENCY, range = 0-100 Hz
Range needed for output = 0-50 Hz
Output signal 0 or 4 mA is needed at 0 Hz (0% of range) - set par.6-51
Terminal 42 Output Min Scale to 0%
Output signal 20 mA is needed at 50 Hz (50% of range) - set par.6-52
Terminal 42 Output Max Scale to 50%
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0-100%
Output signal 0 or 4 mA is needed at 0% (50% of range) - set par.6-51
Terminal 42 Output Min Scale to 50%
Output signal 20 mA is needed at 100% (75% of range) - set par.6-52
Terminal 42 Output Max Scale to 75%
EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA
Output signal 0 or 4 mA is needed at Min ref - set par.6-51
Terminal 42 Output Min Scale to 0%
Output signal 10 mA is needed at Max ref (100% of range) - set par.6-52
Terminal 42 Output Max Scale to 200%
(20 mA / 10 mA x 100%=200%).
Parameter Description
122 TR200 Programming Guide