Illustration 4. 3: Controlled Ramp-down, longer mains failure. Ramping down as long as the energy in the system
allows for it, then the motor is coasted.
Illustration 4. 4: Kinetic Back-up, short mains failure. Ride through as long as the energy in the system allows for
it.
Illustration 4. 5: Kinetic Back-up, longer mains failure. The motor is coasted as soon as the energy in the system
is too low.
14-11 Mains Voltage at Mains Fault
Range: Function:
342. V* [180 - 600 V] This parameter defines the threshold voltage at which the selected func-
tion in par.14-10
Mains Failure should be activated.
Parameter Description
TR200 Programming Guide 153