[2] Initialisation
Select
Initialization
[2] to reset all parameter values to default settings,
except for par.15-03
Power Up's, par.15-04 Over Temp's and par.
15-05
Over Volt's. The frequency converter will reset during the next
power-up.
par.14-22
Operation Mode will also revert to the default setting
Normal
operation
[0].
[3] Boot mode
14-23 Typecode Setting
Option: Function:
Typecode re-writing. Use this parameter to set the typecode matching
the specific FC.
14-25 Trip Delay at Torque Limit
Range: Function:
60 s* [0 - 60 s] Enter the torque limit trip delay in seconds. When the output torque rea-
ches the torque limits (par.4-16
Torque Limit Motor Mode and par.
4-17
Torque Limit Generator Mode), a warning is triggered. When the
torque limit warning has been continuously present for the period speci-
fied in this parameter, the frequency converter trips. Disable the trip
delay by setting the parameter to 60 s = OFF. Thermal frequency con-
verter monitoring will still remain active.
14-26 Trip Delay at Inverter Fault
Range: Function:
0. s* [0 - 35 s] When the frequency converter detects an over-voltage in the set time trip
will be effected after the set time.
14-28 Production Settings
Option: Function:
[0] * No action
[1] Service reset
[2] Set Production Mode
14-29 Service Code
Range: Function:
0 N/A* [-2147483647 -
2147483647 N/A]
Service use only.
Parameter Description