21-38 Ext. 2 Feedback [Unit]
Range: Function:
0.000
Ex-
tPID2Un
it*
[-999999.999 - 999999.999
ExtPID2Unit]
See par.21-18
Ext. 1 Feedback [Unit] for details.
21-39 Ext. 2 Output [%]
Range: Function:
0 %* [0 - 100 %] See par.21-19
Ext. 1 Output [%] for details.
21-4* Closed Loop 2 PID
Configure the Closed Loop 2 PID Controller.
21-40 Ext. 2 Normal/Inverse Control
Option: Function:
See par.21-20
Ext. 1 Normal/Inverse Control for details.
[0] * Normal
[1] Inverse
21-41 Ext. 2 Proportional Gain
Range: Function:
0.01 N/
A*
[0.00 - 10.00 N/A] See par.21-21
Ext. 1 Proportional Gain for details.
21-42 Ext. 2 Integral Time
Range: Function:
10000.0
0 s*
[0.01 - 10000.00 s] See par.21-22
Ext. 1 Integral Time for details.
21-43 Ext. 2 Differentation Time
Range: Function:
0.00 s* [0.00 - 10.00 s] See par.21-23
Ext. 1 Differentation Time for details.
21-44 Ext. 2 Dif. Gain Limit
Range: Function:
5.0 N/A* [1.0 - 50.0 N/A] See par.21-24
Ext. 1 Dif. Gain Limit for details.
Parameter Description
208 TR200 Programming Guide