24-11 Drive Bypass Delay Time
Range: Function:
0 s* [0 - 600 s] Programmable in 1 s increments. Once the Bypass Function is activated
in accordance with the setting in par.24-10
Drive Bypass Function, the
Bypass Delay Timer begins to operate. If the frequency converter has
been set for a number of restart attempts, the timer will continue to run
while the frequency converter tries to restart. Should the motor have re-
started within the time period of the Bypass Delay Timer, then the timer
is reset.
Should the motor fail to restart at the end of the Bypass Delay Time, the
Drive Bypass relay will be activated, which will have been programmed
for Bypass in par.5-40
Function Relay. If a [Relay Delay] has also been
programmed in par.5-41
On Delay, Relay, [Relay] or par.5-42 Off Delay,
Relay, [Relay], then this time must also elapse before the relay action is
performed.
Where no restart attempts are programmed, the timer will run for the
delay period set in this parameter and will then activate the Drive Bypass
relay, which will have been programmed for Bypass in par.5-40
Function
Relay, Function Relay. If a Relay Delay has also been programmed in par.
5-41
On Delay, Relay, On Delay, Relay or par.5-42 Off Delay, Relay, [Re-
lay], then this time must also elapse before the relay action is performed.
Parameter Description
TR200 Programming Guide 241

Table of Contents

Other manuals for Trane TR200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TR200 Series and is the answer not in the manual?

Trane TR200 Series Specifications

General IconGeneral
Input Voltage24 VAC
Frequency Range50/60 Hz
Communication ProtocolsBACnet MS/TP, Modbus RTU
Controller TypeProgrammable
Power Range20 VA
Control MethodPID Control
Enclosure RatingIP20
Operating Temperature32°F to 122°F (0°C to 50°C)
Humidity Range5% to 95% non-condensing