WARNING
Disconnect power before proceeding.
Troubleshooting:
Check fan resistance.
Check soft charge fuses.
IGBT thermal sensor.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and
the motor is missing.
Turn off the frequency converter and check motor
phase U.
WARNING
Disconnect power before proceeding.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and
the motor is missing.
Turn off the frequency converter and check motor
phase V.
WARNING
Disconnect power before proceeding.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and
the motor is missing.
Turn off the frequency converter and check motor
phase W.
WARNING
Disconnect power before proceeding.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short
time period. Let unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communica-
tion fault
The fieldbus on the communication option card is not
working.
WARNING/ALARM 35, Out of frequency
range:
This warning is active if the output frequency has
reached the high limit (set in par. 4-53) or low limit
(set in par. 4-52). In
Process Control, Closed Loop
(. 1-00)
this warning is displayed.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage
to the frequency converter is lost and par.14-10
Mains
Failure is NOT set to OFF. Check the fuses to the fre-
quency converter
ALARM 38, Internal fault
It may be necessary to contact your Trane supplier.
Some typical alarm messages:
0 Serial port cannot be initialized. Serious hardware
failure
256-258 Power EEPROM data is defect or too old
512 Control board EEPROM data is defect or too old
513 Communication time out reading EEPROM data
514 Communication time out reading EEPROM data
515 Application Orientated Control cannot recognize the
EEPROM data
516 Cannot write to the EEPROM because a write com-
mand is on progress
517 Write command is under time out
518 Failure in the EEPROM
519 Missing or invalid Barcode data in EEPROM
783 Parameter value outside of min/max limits
1024-
1279
A can-telegram that has to be sent, couldn't be sent
1281 Digital Signal Processor flash timeout
1282 Power micro software version mismatch
1283 Power EEPROM data version mismatch
1284 Cannot read Digital Signal Processor software ver-
sion
1299 Option SW in slot A is too old
1300 Option SW in slot B is too old
1302 Option SW in slot C1 is too old
1315 Option SW in slot A is not supported (not allowed)
1316 Option SW in slot B is not supported (not allowed)
1318 Option SW in slot C1 is not supported (not allowed)
1379 Option A did not respond when calculating Platform
Version.
1380 Option B did not respond when calculating Platform
Version.
1536 An exception in the Application Orientated Control
is registered. Debug information written in keypad
1792 DSP watchdog is active. Debugging of power part
data Motor Orientated Control data not transferred
correctly
2049 Power data restarted
2064-207
2
H081x: option in slot x has restarted
2080-208
8
H082x: option in slot x has issued a powerup-wait
2096-210
4
H083x: option in slot x has issued a legal powerup-
wait
2304 Could not read any data from power EEPROM
2305 Missing SW version from power unit
2314 Missing power unit data from power unit
2315 Missing SW version from power unit
Troubleshooting
252 TR200 Programming Guide