Note
Remove a warning arising in connection with
Off
[0] or
Warning
[1] by cycling the mains supply. The fault must
be corrected first. For
Off
[0] or
Warning
[1], the frequency converter keeps running even if a fault is located.
2-16 AC brake Max. Current
Range: Function:
100.0
%*
[0.0 - 1000.0 %] Enter the maximum permissible current when using AC brake to avoid
overheating of motor windings. The AC brake function is available in Flux
mode only (FC 302 only).
2-17 Over-voltage Control
Option: Function:
Over-voltage control (OVC) reduces the risk of the frequency converter
tripping due to an over voltage on the DC link caused by generative pow-
er from the load.
[0] Disabled No OVC required.
[2] * Enabled Activates OVC.
NOTE: The ramp time is automatically adjusted to avoid tripping of the frequency converter.
Parameter Description
72 TR200 Programming Guide