3-11 Jog Speed [Hz]
Range: Function:
10.0 Hz* [0.0 - par. 4-14 Hz] The jog speed is a fixed output speed at which the frequency converter
is running when the jog function is activated.
See also par.3-80
Jog Ramp Time.
3-13 Reference Site
Option: Function:
Select which reference site to activate.
[0] * Linked to Hand / Auto Use local reference when in Hand mode; or remote reference when in
Auto mode.
[1] Remote Use remote reference in both Hand mode and Auto mode.
[2] Local Use local reference in both Hand mode and Auto mode.
NOTICE
When set to Local [2], the frequency converter will start with this setting again
following a 'power down'.
Parameter Description
74 TR200 Programming Guide