4-6* Speed Bypass
Define the Speed Bypass areas for the ramps.
Some systems call for avoiding certain output frequencies or speeds, due to resonance problems in the system.
A maximum of four frequency or speed ranges can be avoided.
4-60 Bypass Speed From [RPM]
Array [4]
Range: Function:
0 RPM* [0 - par. 4-13 RPM] Some systems call for avoiding certain output speeds due to resonance
problems in the system. Enter the lower limits of the speeds to be avoi-
ded.
4-61 Bypass Speed From [Hz]
Array [4]
Range: Function:
0 Hz* [0.0 - par. 4-14 Hz] Some systems call for avoiding certain output speeds due to resonance
problems in the system. Enter the lower limits of the speeds to be avoi-
ded.
4-62 Bypass Speed To [RPM]
Array [4]
Range: Function:
0 RPM* [0 - par. 4-13 RPM] Some systems call for avoiding certain output speeds due to resonance
problems in the system. Enter the upper limits of the speeds to be avoi-
ded.
4-63 Bypass Speed To [Hz]
Array [4]
Range: Function:
0 Hz* [0.0 - par. 4-14 Hz] Some systems call for avoiding certain output speeds due to resonance
problems in the system. Enter the upper limits of the speeds to be avoi-
ded.