RMWH-SVX001C-EN 57
Appendix C: Default Settings
Alarm Setpoints
The default settings for the alarm setpoints are the
following:
5, 20, and 50 percent of full-scale range, except for
R123, which are
1, 2, and 5 percent of full-scale range
Non-latching
Horn and strobe (if applicable) enabled
Relays
The default setting for the internal fault relay is the
energized state. All other relays (alarm, warning, caution,
and horn) are set to de-energized.
Output
The default setting for digital output is None. The factory
default settings for analog output are 3.5 mA for Warm-up
and 2.0 mA for Fault.