Calibration
RMWH-SVX001C-EN 29
Unsuccessful Calibrations
In the unlikely event that a problem occurs during a
calibration process, the Results screen will show the
calibration status as Unsuccessful.
1. On the Results screen, s
elect Co
ntinue.
2. On the Calibration Unsuccessful screen, do one of
the following:
a. For zero gas calibrations:
i. To retry the zero gas calibration, select Repeat
Calibra
tion.
ii. To return to the previous calibration values,
select Close.
b. For span gas calibrations:
i. To do a span gas calibration for another gas,
select Select Another Gas.
ii.
To retry the span gas calibration, select Repeat
Ca
libration.
iii. To return to the previous calibration values,
select Close.
If Close is se
lected
, on the dashboard, a gray check
mark indentifies the points that are affected by the
unsuccessful calibration. The gas readings for these
sample points are below the alarm threshold but may
not be completely accurate.