Appendix E: BACnet Objects
RMWH-SVX001C-EN 65
Channel Status Flags
Bit Description
0x0001 Caution Set if caution level is achieved
0x0002 Warning
Set if warning level is achieved
0x0004 Alarm Set if alarm level is achieved
0x0008 Beacon
Set if C/W/A is set
0x0010 Horn Set if any configured C/W/A is set and not acknowledged yet
0x0020 New
Set if any of C/W/A is set and not acknowledged yet
0x0040 Hold Set if any of C/W/A is in hold state (acknowledged latching alarm below threshold)
0x0080 Fault
Set if failure is reported
0xFF00 — Reserved
Gas Types
Value Name
Gases
0 R-11
1
R-12
2 R-22
3
R-123
4 R-134A
5
R-401A
6 R-404A
7
R-407A
8 R-407C
9
R-407F
10 R-410A
11
R-422A
12 R-422D
13
R-427A
14 R-507
15
R-513A
16 R-514A
17
R-1233zd(E)
18 R-1234yf
19 R-1234ze